Description
The System-40 provides highly accurate thermal energy measurement in chilled water, hot water or condenser water systems. It is provided as a complete meter and includes a matched pair of platinum RTD temperature sensors and an integral inline ultrasonic flow sensor. It is available for use in ½” through 2½” piping systems with flow rates ranging from 0.03 to 250 GPM.
Application
Monitoring chilled water, hot water and condenser water in AHU and CRAC units for:
- Commercial office tenant billing
- Residential apartment and condominium tenant billing
Monitoring renewable energy resources for:
- Solar thermal applications
- Ground source heat pumps
- Geothermal heating systems
Features
- Reliable No-Moving-Parts Design –
-
Wetted transducers measure the ultrasonic signal transit time differential, which correlates directly to the flow rate. The direct beam path orientation significantly enhances signal strength and long term reliability.
-
- Highly Accurate Over a Wide Flow Range –
-
The flow sensor is accurate to within ±1% of reading over the normal (25:1 turndown)
-
operating range and within ±2% of reading over an extended (100:1 turndown) range.
-
- User-Friendly Backlit Display –
-
The bright, easy-to-read, backlit display uses “smart button technology” to simplify page navigation and programming. This eliminates the need for special configuration tools.
-
- Matched Platinum 1000Ω RTD Temperature Sensors
-
Sensors are paired in a matching process that ensures a differential measurement uncertainty of better than ±0.18°F.
-
- Suitable for Water and Water/Glycol Solutions
-
System-40 is field programmable for both water and water/glycol solutions to ensure accurate flow and energy measurement.
-
- Detachable Display
-
The display for the system-40 is easily detached from the flow sensor. This allows for remote mount installation up to 5ft from the sensor body.
-
- Built-in Interval Data Logger
-
Energy and volume totals are date/time stamped and logged within the meter along with other analytical data. This data is available via BACnet®.
-
- ACCURACY
-
±1% of reading over 25:1 turndown
-
±2% of reading over 100: 1 turndown
-
Overall turndown exceeds 500: 1
-
Repeatability: ≤±0.2%
-
Meets EN1434 Class 1 accuracy requirements
-
- TEMPERATURE SENSORS
-
Field serviceable MID certified matched pair of 2-wire 1000Ω platinum RTDs
-
Calibrated to a differential measurement uncertainty of ±0.18°F
-
Meets EN1434/C900.1 accuracy requirements for 3K sensors
-
- CALCULATOR
-
Computation error: ≤ 0.09% at 30°F Δt
-
Meets EN1434 Class 1 requirements with 3K minimum Δt
-
- PIPE SIZE RANGE
-
½ – 2½” nominal diameter
-
- PIPING SYSTEM CONNECTIONS
-
Male NPT threads
-
2½” meter provided with ANSI Class 150 raised face flanges
-
- FLUID TEMPERATURE RANGE
-
32 to 250°F
-
- MAXIMUM OPERATING PRESSURE
-
400 psi
-
- PRESSURE DROP
-
Less than 1 psi at 4 ft/s, decreasing at lower velocities
-
- MATERIALS
-
Wetted components: Lead-free brass, PEEK
-
Enclosure: Polycarbonate
-
- ENVIRONMENTAL
-
Meets EN1434/C900.1 Class A requirements
-
Operating Temperature Range: -13 to 131°F
-
Storage Temperature Range: -14 to 158°F
-
Enclosure Rating: IP65
-
- POWER SUPPLY REQUIREMENTS
-
20-28V AC/DC, 50/60 Hz, 5 VA maximum
-
- ISOLATED ANALOG OUTPUT
-
Maybe programmable for energy rate, flow rate, supply temperature, return temperature or Δt
-
Configurable as: 4-20mA, 0-5 V or 0-10 V output
-
- ISOLATED TOTALIZING SOLID STATE CONTACT CLOSURE PULSE OUTPUTS
-
Maybe programmed for energy, volume, alarm indication, mode indication or MODBUS coil indication
-
Contact ratings: 50 mA, 30 V
-
Contact pulse duration: 50, 100, 500 or 1000 ms
-
- ISOLATED TOTALIZING PULSE INPUTS
-
For use with sinking open collector or dry contact outputs
-
Input rating: 30 VDC, 10 mA maximum
-
Pulse duration: 50 ms minimum
-
- NETWORK CONNECTIONS
-
Isolated RS485 serial interface
-
- COMMUNICATION PROTOCOLS
-
BACnet® MS/TP per ASHRAE Standard 135.1: 2009
-
MODBUS® RTU
-
- NETWORK CONFIGURATION & ADDRESSING
-
Baud Rates: 4800, 9600, 19200, 38400, 76800, or 115200
-
Device Address Range: 1 – 255 (1 – 247 MODBUS® RTU)
-
Device Instance Range: 1 – 4,194,303 (BACnet® only)
-
Parity: None, Even, Odd (MODBUS® RTU only)
-
For More information please contact our Email : Marketing@wmablog.com